Calculate derated capacity by multiplying a base rating by temperature, conductor-grouping and site derating factors, or find the base rating you need.

Multiply applicable correction factors; 100% means no adjustment.

All capacities use this unit. Changing it reinterprets the numbers; it does not convert them.

NEC Table 310.15(C)(1) adjustment for conductors in one raceway or cable; choose Custom for other standards.

Optional load check
Blank omits the load check; an entered zero is a zero load.

Select 1.25 only when the governing rule requires it.


Related Calculators

Calculator Functions

FunctionWhat it doesWhat it requires
Derated capacityFinds the capacity left after temperature, grouping and site factors are applied to a base ratingRequires the base or nameplate capacity and the three factors as percentages
Required base capacityFinds the base rating needed to still deliver a target capacity after deratingRequires the target derated capacity and the three factors as percentages
Missing site factorFinds the site factor that brings a base rating down to a target capacityRequires the base capacity, the target capacity, the temperature factor and the grouping factor

Every function works in one capacity unit: amps, kW, kVA, watts or another unit. The unit is a label only, so changing it does not convert the numbers. The grouping factor comes from a list based on how many current-carrying conductors run together, or from a custom percentage. An optional load check multiplies a design load by 1 or 1.25 and by an added margin, then compares it with the derated capacity.

Derating Factor Formulas

Cd = Cb ร— Ft ร— Fg ร— Fs
CdDerated capacity, in the chosen unit
CbBase or nameplate capacity, in the same unit
FtTemperature factor (percent รท 100)
FgGrouping factor (percent รท 100) [1]
FsSite or custom factor (percent รท 100)

A factor of 100% means no adjustment. The product of the three factors is shown as the combined factor, with the capacity reduction as a percentage. A combined factor above 100% raises the rating, and the calculator flags it because an increase needs support from the equipmentโ€™s own data.

Derated capacity

The main formula applies directly. A 100 A base rating with an 88% temperature factor, the 80% grouping factor for 4โ€“6 conductors and a 100% site factor gives 100 ร— 0.88 ร— 0.80 ร— 1.00 = 70.4 A.

Required base capacity

Cb = Cd รท (Ft ร— Fg ร— Fs)

A 70.4 A target under the same factors needs 70.4 รท 0.704 = 100 A of base rating. The target must be above zero.

Missing site factor

Fs = Cd รท (Cb ร— Ft ร— Fg)

Reaching 60 A from a 100 A base with factors of 88% and 80% needs a site factor of 60 รท 70.4 = 85.23%.

Grouping factors

Current-carrying conductors togetherGrouping factor
1โ€“3100%
4โ€“680%
7โ€“970%
10โ€“2050%
21โ€“3045%
31โ€“4040%
41 or more35%

The 4โ€“6 row and below are the adjustment factors of NEC Table 310.15(C)(1) for more than three current-carrying conductors in one raceway or cable [1]. For another standard, choose the custom grouping factor and enter its percentage.

Load check

Required = load ร— k ร—
(1 + margin รท 100)

k is the load multiplier, 1 or 1.25. A 50 A load at 1.25 with a 10% margin requires 68.75 A, which is within a 70.4 A derated capacity at about 97.7% utilization. Leaving the design load blank skips the check. The 1.25 multiplier belongs only where the governing rule calls for it.

Temperature Derating Factor

DF = (Tmax โˆ’ Ta) รท (Tmax โˆ’ Tr)

Datasheet derating curves are commonly drawn as a straight line from full rated power at a rated temperature Tr down to zero at the maximum operating temperature Tmax [2]. On such a line, DF is the fraction of the rating left at ambient temperature Ta, and at or below Tr the full rating applies. With Tmax = 150 ยฐC, Tr = 25 ยฐC and Ta = 35 ยฐC, DF = 115 รท 125 = 0.92, which goes into the calculator as a temperature factor of 92%. The calculator does not work this factor out from temperatures.

Limits of This Estimate

  • The result is arithmetic on the entered factors. It does not establish installation safety, protective-device sizing or code compliance.
  • All factors must apply to the same equipment and the same rating basis. A condition already built into the base rating must not be counted a second time.
  • Amps, kW and kVA cannot be converted into one another without data on the electrical system, so every capacity must be entered in one unit.
  • The straight-line temperature formula is a datasheet convention, and it holds only where the manufacturer specifies such a curve for the device. These estimates are based on the best available data and estimations.

Sources