Calculate derated capacity by multiplying a base rating by temperature, conductor-grouping and site derating factors, or find the base rating you need.
Related Calculators
- Heat Dissipation Calculator
- Wire Resistance Calculator
- Resistor Heat Calculator
- Inverter Capacity Calculator
- All Physics Calculators
Calculator Functions
| Function | What it does | What it requires |
|---|---|---|
| Derated capacity | Finds the capacity left after temperature, grouping and site factors are applied to a base rating | Requires the base or nameplate capacity and the three factors as percentages |
| Required base capacity | Finds the base rating needed to still deliver a target capacity after derating | Requires the target derated capacity and the three factors as percentages |
| Missing site factor | Finds the site factor that brings a base rating down to a target capacity | Requires the base capacity, the target capacity, the temperature factor and the grouping factor |
Every function works in one capacity unit: amps, kW, kVA, watts or another unit. The unit is a label only, so changing it does not convert the numbers. The grouping factor comes from a list based on how many current-carrying conductors run together, or from a custom percentage. An optional load check multiplies a design load by 1 or 1.25 and by an added margin, then compares it with the derated capacity.
Derating Factor Formulas
| Cd | Derated capacity, in the chosen unit |
| Cb | Base or nameplate capacity, in the same unit |
| Ft | Temperature factor (percent รท 100) |
| Fg | Grouping factor (percent รท 100) [1] |
| Fs | Site or custom factor (percent รท 100) |
A factor of 100% means no adjustment. The product of the three factors is shown as the combined factor, with the capacity reduction as a percentage. A combined factor above 100% raises the rating, and the calculator flags it because an increase needs support from the equipmentโs own data.
Derated capacity
The main formula applies directly. A 100 A base rating with an 88% temperature factor, the 80% grouping factor for 4โ6 conductors and a 100% site factor gives 100 ร 0.88 ร 0.80 ร 1.00 = 70.4 A.
Required base capacity
A 70.4 A target under the same factors needs 70.4 รท 0.704 = 100 A of base rating. The target must be above zero.
Missing site factor
Reaching 60 A from a 100 A base with factors of 88% and 80% needs a site factor of 60 รท 70.4 = 85.23%.
Grouping factors
| Current-carrying conductors together | Grouping factor |
|---|---|
| 1โ3 | 100% |
| 4โ6 | 80% |
| 7โ9 | 70% |
| 10โ20 | 50% |
| 21โ30 | 45% |
| 31โ40 | 40% |
| 41 or more | 35% |
The 4โ6 row and below are the adjustment factors of NEC Table 310.15(C)(1) for more than three current-carrying conductors in one raceway or cable [1]. For another standard, choose the custom grouping factor and enter its percentage.
Load check
(1 + margin รท 100)
k is the load multiplier, 1 or 1.25. A 50 A load at 1.25 with a 10% margin requires 68.75 A, which is within a 70.4 A derated capacity at about 97.7% utilization. Leaving the design load blank skips the check. The 1.25 multiplier belongs only where the governing rule calls for it.
Temperature Derating Factor
Datasheet derating curves are commonly drawn as a straight line from full rated power at a rated temperature Tr down to zero at the maximum operating temperature Tmax [2]. On such a line, DF is the fraction of the rating left at ambient temperature Ta, and at or below Tr the full rating applies. With Tmax = 150 ยฐC, Tr = 25 ยฐC and Ta = 35 ยฐC, DF = 115 รท 125 = 0.92, which goes into the calculator as a temperature factor of 92%. The calculator does not work this factor out from temperatures.
Limits of This Estimate
- The result is arithmetic on the entered factors. It does not establish installation safety, protective-device sizing or code compliance.
- All factors must apply to the same equipment and the same rating basis. A condition already built into the base rating must not be counted a second time.
- Amps, kW and kVA cannot be converted into one another without data on the electrical system, so every capacity must be entered in one unit.
- The straight-line temperature formula is a datasheet convention, and it holds only where the manufacturer specifies such a curve for the device. These estimates are based on the best available data and estimations.
Sources
- Elliott Electric Supply, Maximum Current Adjustment Factors for More Than 3 Current Carrying Wire Conductors (2020 NEC Table 310.15(C)(1)): grouping percentages by number of conductors
- Vishay Sfernice, Application Note 53048, Power Dissipation in High Precision Chip Resistors and Arrays: straight-line derating from rated power to zero at the maximum temperature
