Calculate feeder size in copper or aluminum from load amps, voltage, run length and a 3% voltage drop, or find the maximum run for a chosen wire size.
Calculator Functions
| Function | What it does | What it requires |
|---|---|---|
| Feeder conductor size | Finds the smallest copper or aluminum conductor that passes a current check and a voltage drop check | Requires the continuous load, the noncontinuous load, the system voltage, the circuit model, the conductor material, the one-way run length and the allowed voltage drop |
| Maximum run length for a conductor size | Finds the longest one-way run a chosen conductor can serve within the allowed voltage drop | Requires the continuous load, the noncontinuous load, the system voltage, the circuit model, the conductor material, the selected conductor size and the allowed voltage drop |
Loads are in amps, and either load can be left blank if there is none. The circuit model is single-phase or two-wire DC, or balanced three-phase. Run length can be in feet or meters. The allowed voltage drop starts at 3% and the voltage accepts up to 600 V. Results also show the screening current, the voltage drop in volts and percent, the voltage at the load and the size each check asks for on its own.
Feeder Size Formulas
| FS | Conductor area needed for voltage drop (circular mils) |
| m | 2 for single-phase or two-wire DC, 1.732 (√3) for balanced three-phase |
| K | Resistance constant at 75 °C: 12.9 for copper, 21.2 for aluminum (Ω·cmil/ft) |
| I | Load current, continuous plus noncontinuous, at 100% (A) |
| L | One-way run length (ft) |
| VD | Allowed voltage drop: system voltage × percent ÷ 100 (V) |
This is the voltage drop formula VD = m × K × I × L ÷ CM solved for the conductor area [1]. K is the direct-current resistance of a conductor one circular mil in area and one foot long at 75 °C. It suits alternating current only up to about 1/0 AWG; larger conductors lose more to self-induction than the formula shows [1]. The current is the actual load, not the load raised to 125% [1].
Feeder conductor size
Inoncont
The calculator runs two checks and reports the larger size. The current check finds the smallest conductor whose 75 °C ampacity is at least the screening current Is, which counts a continuous load (one running 3 hours or more) at 125%. The voltage drop check finds the smallest conductor with at least FS circular mils. For 80 A of noncontinuous load at 240 V single-phase on a 100 ft copper run with 3% allowed, VD = 7.2 V and FS = 2 × 12.9 × 80 × 100 ÷ 7.2 = 28,667 cmil. That needs 4 AWG (41,740 cmil), and 4 AWG copper carries 85 A, so the answer is 4 AWG copper. If the same 80 A is continuous, the screening current is 100 A and the answer moves up to 3 AWG.
Maximum run length for a conductor size
CM is the circular mil area of the selected conductor. A 44 A noncontinuous load at 240 V single-phase on 6 AWG copper (26,240 cmil) with 3% allowed can run 7.2 × 26,240 ÷ (2 × 12.9 × 44) = 166.4 ft one way. The result also says whether that conductor passes the current check. A length that passes voltage drop does not make an undersized conductor acceptable.
Feeder Size Chart
These are the areas and 75 °C ampacities the calculator checks against [2][3]. For 12 and 10 AWG it uses the lower limits of 20 A and 30 A for copper and 15 A and 25 A for aluminum.
| Size | Area (cmil) | Copper (A) | Aluminum (A) |
|---|---|---|---|
| 12 AWG | 6,530 | 20 | 15 |
| 10 AWG | 10,380 | 30 | 25 |
| 8 AWG | 16,510 | 50 | 40 |
| 6 AWG | 26,240 | 65 | 50 |
| 4 AWG | 41,740 | 85 | 65 |
| 3 AWG | 52,620 | 100 | 75 |
| 2 AWG | 66,360 | 115 | 90 |
| 1 AWG | 83,690 | 130 | 100 |
| 1/0 AWG | 105,600 | 150 | 120 |
| 2/0 AWG | 133,100 | 175 | 135 |
| 3/0 AWG | 167,800 | 200 | 155 |
| 4/0 AWG | 211,600 | 230 | 180 |
| 250 kcmil | 250,000 | 255 | 205 |
| 300 kcmil | 300,000 | 285 | 230 |
| 350 kcmil | 350,000 | 310 | 250 |
| 400 kcmil | 400,000 | 335 | 270 |
| 500 kcmil | 500,000 | 380 | 310 |
| 600 kcmil | 600,000 | 420 | 340 |
| 700 kcmil | 700,000 | 460 | 375 |
| 750 kcmil | 750,000 | 475 | 385 |
| 800 kcmil | 800,000 | 490 | 395 |
| 900 kcmil | 900,000 | 520 | 425 |
| 1000 kcmil | 1,000,000 | 545 | 445 |
Limits of This Estimate
- This is a planning check, not approval of an installation. A qualified person has to check the adopted electrical code and the actual installation.
- Ampacities assume 75 °C terminations and insulation, a 30 °C ambient temperature and no more than three current-carrying conductors in a raceway or cable [3]. Higher temperatures and more conductors lower them.
- The 3% feeder voltage drop is a recommendation in the National Electrical Code, not an enforceable rule. The same note recommends no more than 5% for feeder and branch circuit together [1].
- The voltage drop is resistance only. It leaves out reactance and power factor, so it understates the drop on large AC conductors.
- Demand factors, overcurrent protection, neutral and grounding conductors, motor and dwelling rules and parallel conductors are not covered. Loads above 545 A in copper or 445 A in aluminum are outside the table.
- The 125% continuous-load rule and the 12 and 10 AWG limits are stated as the calculator applies them. These estimates are based on the best available data and estimations.
Sources
- Mike Holt Enterprises, Voltage Drop Calculations, Part One: voltage drop formula, the K constants for copper and aluminum, and the 3% feeder recommendation
- Cerrowire, Ampacity Charts: 75 °C ampacities for copper and aluminum conductors
- Southwire, SPEC 10016, XHHW-2 Aluminum, Table 2: 75 °C aluminum ampacities based on 2023 NEC Table 310.16
