Calculate 3-phase delta power, line current or line voltage from the other values and power factor, and convert between delta line and phase current.

Use RMS line-to-line voltage and RMS line current for a balanced delta-connected load.

0.8 is a common assumption for motor loads; use your nameplate or measured value if known. Enter 80% as 0.8.

Optional settings

Calculator Functions

FunctionWhat it doesWhat it requires
Real and apparent powerFinds the total real power in watts and the apparent power in volt-amperes of a balanced delta loadRequires the line-to-line RMS voltage, the RMS line current and the power factor
Line current from real powerFinds the RMS line current that carries a known real powerRequires the total real power, the line-to-line RMS voltage and the power factor
Line voltage from real powerFinds the line-to-line RMS voltage needed for a known real powerRequires the total real power, the RMS line current and the power factor
Phase current from line currentFinds the current in each branch of the deltaRequires the RMS line current
Line current from phase currentFinds the current in each supply line from the branch currentRequires the RMS phase (branch) current

Voltage is entered in V or kV, current in A, mA or kA and power in W or kW. Power factor is a decimal from 0 to 1 and starts at 0.8, so 80% goes in as 0.8. The three power functions list apparent power, real power, line voltage, line current and phase current together.

3 Phase Delta Formulas

P = √3 × V × I × PF [1]
PTotal real power of the three phases (W)
VLine-to-line RMS voltage (V). In a delta, each branch sees this full voltage [1]
IRMS line current (A)
PFPower factor, from 0 to 1

Each branch of a delta carries the line current divided by √3 and sits across the full line voltage [1]. The power in one phase is voltage × current × power factor, and the total is the sum of the three phases [1]. Three branches at V × (I ÷ √3) × PF add up to √3 × V × I × PF.

Real and apparent power

S = √3 × V × I

S is the apparent power in VA, and real power is P = S × PF. At 400 V, 10 A and a power factor of 0.8, S = 6,928.2 VA and P = 5,542.56 W. At a power factor of 1 the two are equal.

Line current from real power

I = P ÷ (√3 × V × PF)

This is the main formula solved for current. A load drawing 5,542.56 W at 400 V and a power factor of 0.8 takes 10 A per line. The power factor and the voltage must both be above zero.

Line voltage from real power

V = P ÷ (√3 × I × PF)

This is the main formula solved for voltage. A 10,000 W load at 15 A and a power factor of 0.9 needs 427.67 V between lines. The power factor and the current must both be above zero.

Phase current from line current

Iph = I ÷ √3 [1]

Iph is the current in one branch of the delta. A line current of 10 A gives 5.7735 A in each branch.

Line current from phase current

I = √3 × Iph [1]

Each supply line feeds two branches, so the line current is larger than the branch current by a factor of √3, about 1.73. A branch current of 10 A gives 17.3205 A in each line.

Limits of This Estimate

  • Assumes a balanced load with sinusoidal voltage and current. Unbalanced loads and harmonics need a phase-by-phase analysis.
  • The power formulas use line quantities, so they also describe a balanced wye load. The phase current functions are for delta only: in a wye, phase current equals line current [1].
  • The starting power factor of 0.8 is a placeholder. A nameplate or measured value gives a better answer.
  • The results are circuit quantities. They do not size conductors, breakers or equipment.

Sources

  1. U.S. Department of Energy, DOE Fundamentals Handbook, Electrical Science, Volume 4 (DOE-HDBK-1011/4-92): delta and wye line and phase relations (Module 13, Table 1), single-phase power and total three-phase power as the sum of the phases (Module 14)