Calculate 3-phase delta power, line current or line voltage from the other values and power factor, and convert between delta line and phase current.
- All Physics Calculators
- 3 Phase Fault Current Calculator
- 3 Phase Horsepower Calculator
- 3 Phase Motor Capacitor Calculator
Calculator Functions
| Function | What it does | What it requires |
|---|---|---|
| Real and apparent power | Finds the total real power in watts and the apparent power in volt-amperes of a balanced delta load | Requires the line-to-line RMS voltage, the RMS line current and the power factor |
| Line current from real power | Finds the RMS line current that carries a known real power | Requires the total real power, the line-to-line RMS voltage and the power factor |
| Line voltage from real power | Finds the line-to-line RMS voltage needed for a known real power | Requires the total real power, the RMS line current and the power factor |
| Phase current from line current | Finds the current in each branch of the delta | Requires the RMS line current |
| Line current from phase current | Finds the current in each supply line from the branch current | Requires the RMS phase (branch) current |
Voltage is entered in V or kV, current in A, mA or kA and power in W or kW. Power factor is a decimal from 0 to 1 and starts at 0.8, so 80% goes in as 0.8. The three power functions list apparent power, real power, line voltage, line current and phase current together.
3 Phase Delta Formulas
| P | Total real power of the three phases (W) |
| V | Line-to-line RMS voltage (V). In a delta, each branch sees this full voltage [1] |
| I | RMS line current (A) |
| PF | Power factor, from 0 to 1 |
Each branch of a delta carries the line current divided by √3 and sits across the full line voltage [1]. The power in one phase is voltage × current × power factor, and the total is the sum of the three phases [1]. Three branches at V × (I ÷ √3) × PF add up to √3 × V × I × PF.
Real and apparent power
S is the apparent power in VA, and real power is P = S × PF. At 400 V, 10 A and a power factor of 0.8, S = 6,928.2 VA and P = 5,542.56 W. At a power factor of 1 the two are equal.
Line current from real power
This is the main formula solved for current. A load drawing 5,542.56 W at 400 V and a power factor of 0.8 takes 10 A per line. The power factor and the voltage must both be above zero.
Line voltage from real power
This is the main formula solved for voltage. A 10,000 W load at 15 A and a power factor of 0.9 needs 427.67 V between lines. The power factor and the current must both be above zero.
Phase current from line current
Iph is the current in one branch of the delta. A line current of 10 A gives 5.7735 A in each branch.
Line current from phase current
Each supply line feeds two branches, so the line current is larger than the branch current by a factor of √3, about 1.73. A branch current of 10 A gives 17.3205 A in each line.
Limits of This Estimate
- Assumes a balanced load with sinusoidal voltage and current. Unbalanced loads and harmonics need a phase-by-phase analysis.
- The power formulas use line quantities, so they also describe a balanced wye load. The phase current functions are for delta only: in a wye, phase current equals line current [1].
- The starting power factor of 0.8 is a placeholder. A nameplate or measured value gives a better answer.
- The results are circuit quantities. They do not size conductors, breakers or equipment.
Sources
- U.S. Department of Energy, DOE Fundamentals Handbook, Electrical Science, Volume 4 (DOE-HDBK-1011/4-92): delta and wye line and phase relations (Module 13, Table 1), single-phase power and total three-phase power as the sum of the phases (Module 14)
