Calculate 3-phase fault current from line-to-line voltage and total impedance or from short-circuit MVA, or solve back for the voltage or impedance.
- All Physics Calculators
- 3 Phase Horsepower Calculator
- 3 Phase Motor Capacitor Calculator
- 3 Phase Ohm’s Law Calculator
Calculator Functions
| Function | What it does | What it requires |
|---|---|---|
| 3-phase fault current | Finds the symmetrical RMS current of a bolted three-phase fault | Requires line-to-line voltage and total per-phase impedance |
| 3-phase voltage (I, Z) | Finds the line-to-line voltage behind a fault current | Requires fault current and total per-phase impedance |
| 3-phase impedance | Finds the total per-phase impedance to the fault | Requires line-to-line voltage and fault current |
| 1-phase fault current | Finds the fault current in a single-phase loop | Requires the voltage across the fault loop and total loop impedance |
| 1-phase loop voltage | Finds the voltage across a single-phase fault loop | Requires fault current and total loop impedance |
| 1-phase loop impedance | Finds the total impedance of a single-phase fault loop | Requires loop voltage and fault current |
| 3-phase current (MVA) | Converts a short-circuit level to fault current | Requires line-to-line voltage and short-circuit level |
| 3-phase voltage (MVA) | Finds the line-to-line voltage from a short-circuit level | Requires short-circuit level and fault current |
| 3-phase short-circuit MVA | Converts fault current to a short-circuit level | Requires line-to-line voltage and fault current |
Voltage is entered in V or kV, impedance in Ω or mΩ, current in A or kA and short-circuit level in MVA or kVA. The voltage fields list common system voltages from 120 V to 34,500 V. Every input must be greater than zero.
3 Phase Fault Current Formulas
| I | Symmetrical RMS fault current (A) |
| V | Line-to-line RMS voltage (V) |
| Z | Total impedance of one phase from the source to the fault (Ω): source, transformer and conductors |
In a balanced three-phase fault each phase has the line-to-neutral voltage, V ÷ √3, across its own impedance, so the formula is Ohm’s law for one phase. The same 1.732 factor ties three-phase kVA, line-to-line voltage and line current together in transformer full-load calculations [1].
3-phase fault current
At 480 V with 2 Ω per phase, I = 480 ÷ (1.732 × 2) = 138.56 A. With 20 mΩ per phase, which is closer to the secondary of a large transformer, the same voltage gives 13,856 A.
3-phase voltage (I, Z)
A 138.56 A fault through 2 Ω per phase corresponds to 480 V line to line.
3-phase impedance
A 480 V system that delivers 138.56 A into a bolted fault has 2 Ω per phase between the source and the fault.
1-phase fault current
V is the voltage across the whole fault loop and Zloop is the impedance of the source, the outgoing conductor, the return path and the fault itself. A 120 V loop with 0.5 Ω gives 240 A. This is a plain loop calculation, not a model of a line-to-ground fault on a three-phase network. For those, one manufacturer’s guide puts a bolted line-to-neutral or line-to-ground fault at 25% to 125% of the three-phase value, and a line-to-line fault at 87% [1].
1-phase loop voltage
A 240 A fault through a 0.5 Ω loop corresponds to 120 V.
1-phase loop impedance
120 V driving 240 A means a total loop impedance of 0.5 Ω.
3-phase current (MVA)
S is the three-phase short-circuit level in MVA, as a utility often states it. A 100 MVA level at 13,800 V is 100,000,000 ÷ (1.732 × 13,800) = 4,183.7 A. It is the same relation as transformer full-load current, kVA × 1,000 ÷ (voltage × 1.732) [1].
3-phase voltage (MVA)
A 100 MVA level with 4,183.7 A of fault current corresponds to 13,800 V line to line.
3-phase short-circuit MVA
4,183.7 A at 13,800 V is a short-circuit level of 100 MVA.
Limits of This Estimate
- The result is the symmetrical RMS current of a bolted fault at nominal voltage. It leaves out DC offset, peak current, motor contribution and voltage above nominal. The manufacturer’s guide adds motor contribution separately and notes that utility voltage can run 10% high [1].
- Z has to be the total impedance up to the fault, not the impedance of the fault alone. A transformer’s marked impedance can differ from its actual value by 10%, which moves the fault current by about the same amount [1].
- An arcing fault draws less than a bolted one: the guide puts a sustained three-phase arcing fault at up to 89% of the bolted value [1].
- These are the basic circuit relations, with none of the correction factors a full study applies. These estimates are based on the best available data and estimations. Equipment ratings, protection settings and arc-flash work need a full short-circuit study.
Sources
- Cooper Bussmann, Electrical Plan Review, Bulletin EPR-1 (2002): the 1.732 relation between three-phase kVA, voltage and current, bolted and arcing fault percentages, motor contribution and voltage and impedance tolerances
