Calculate the dehumidifier airflow (CFM) a room needs from its dimensions or volume at 3 air changes per hour, or the room volume an airflow can serve.

ACH measures air circulation, not water-removal capacity (pints/day).

Prefilled with a typical 8 ft ceiling; change it if yours differs.

Air changes per hour (optional)
Blank means 3 ACH.


Related Calculators

Dehumidifier Airflow (ACH) Formula

This calculator uses 3 air changes per hour (ACH) as the default target. It calculates either the airflow rate needed for a room or the room volume that a given airflow rate can handle.

CFM = (V ร— ACH) / 60
V = (CFM ร— 60) / ACH

With the calculator default of 3 ACH, the formulas become:

CFM = (V ร— 3) / 60
V = (CFM ร— 60) / 3
  • CFM = airflow rate in cubic feet per minute
  • V = total room or space volume in cubic feet
  • ACH = air changes per hour
  • 60 = minutes per hour

Choose Airflow to enter room dimensions or volume, or Room volume to enter airflow. Results use 3 ACH unless you enter another rate. Inputs are converted with exact foot/metre factors and then displayed in the selected result unit. This does not establish water-removal capacity or a maximum suitable room size.

Illustrative Air-Circulation Rates

The rates below illustrate airflow calculations only. They are not dehumidifier sizing recommendations; choose the circulation target for the actual design and assess moisture-removal capacity separately.

Condition Illustrative ACH Notes
Example 1 1 to 2 ACH At 1 to 2 ACH, Q = V/60 to V/30 per minute.
Calculator assumption 3 ACH This is the value used by the calculator.
Example 2 3 to 5 ACH At 3 to 5 ACH, Q = V/20 to V/12 per minute.
Example 3 5+ ACH At 5 ACH, Q = V/12 per minute; higher targets require proportionally more airflow.

Quick Volume and Airflow Reference at 3 ACH

Space Volume Required Airflow at 3 ACH
500 ftยณ 25 CFM
1,000 ftยณ 50 CFM
2,000 ftยณ 100 CFM
3,000 ftยณ 150 CFM
5,000 ftยณ 250 CFM

Example Calculations

Example 1: Find the airflow rate

You have a room with a total volume of 2,400 ftยณ. Using 3 ACH:

CFM = (2400 ร— 3) / 60 = 120

The required airflow rate is 120 CFM.

Example 2: Find the supported volume

You have a dehumidifier airflow rate of 80 CFM. Using 3 ACH:

V = (80 ร— 60) / 3 = 1600

80 CFM corresponds to 1,600 ftยณ at the assumed 3 ACH; moisture-removal suitability requires a separate assessment.

FAQ

What does ACH mean for a dehumidifier?

ACH means air changes per hour. For dehumidification, it describes how many times the air volume of the space passes through the dehumidifier each hour. A target of 3 ACH means the airflow should move three times the room volume in one hour.

How do I find the total volume of a room?

For a rectangular room, multiply length by width by height. For example, a 20 ft by 15 ft room with an 8 ft ceiling has a volume of 2,400 ftยณ. For irregular spaces, split the area into smaller rectangular sections, calculate each section, then add them together.

Is airflow the same as dehumidifier capacity?

No. Airflow is how much air the unit moves, usually in CFM or mยณ/min. Dehumidifier capacity is how much water the unit can remove, often listed in pints per day or liters per day. Both matter. A unit can have enough water-removal capacity but still perform poorly if air does not circulate well through the space.