Correct brewing hydrometer SG, calculate free-air and Bouguer anomalies, or adjust indicated mass for local gravity and air buoyancy with visible terms.

Water-density approximation; use your hydrometer manufacturerโ€™s correction table for instrument-specific accuracy.

Brewing Temperature Correction Formula

The following formula approximates a hydrometer temperature correction in Specific Gravity (SG), assuming water-like liquid expansion and neglecting hydrometer glass expansion. This calculator accepts and returns SG; it does not convert ยฐPlato.

SGcorr = SGโ‚˜โ‚‘โ‚โ‚› ร— (ฯw(Tref)) / (ฯw(Tโ‚˜โ‚‘โ‚โ‚›))

Variables:

  • SGcorr is the temperature-corrected specific gravity (dimensionless)
  • SGmeas is the measured specific gravity at the sample temperature (dimensionless)
  • ฯw(T) is the density of pure water at temperature T (kg/mยณ)
  • Tmeas is the sample temperature (ยฐC)
  • Tref is the instrument calibration/reference temperature (ยฐC)

Note: hydrometer temperature correction can be instrument-specific (and may include glass expansion and wort thermal expansion). For best accuracy, use the manufacturerโ€™s correction table. This calculator uses a water-density approximation over a numerical temperature range of 0โ€“100ยฐC. That range does not establish hydrometer accuracy; prefer measurement near calibration temperature and the manufacturerโ€™s instrument/liquid correction table.

What is Gravity Correction?

โ€œGravity correctionโ€ can mean different things depending on context. In brewing, it usually means adjusting a hydrometer gravity reading for temperature differences from the hydrometerโ€™s calibration temperature (commonly 20ยฐC or 60ยฐF). In geophysics, gravity corrections are applied to measured gravitational acceleration to help compute anomalies (such as free-air and Bouguer anomalies). In mass metrology, instrument calibration determines whether a local-gravity correction is needed. A locally calibrated comparison cancels gravity, while the modeled force-responsive scale calibrated against reference weights at standard gravity requires the stated g0/local-gravity factor. Both mass paths assume identical air density during calibration and use.

How to Calculate Corrected Gravity?

The following steps outline how to calculate a brewing temperature-corrected gravity reading.


  1. Measure the hydrometer reading as Specific Gravity (SG).
  2. Record the sample temperature (Tmeas) and the hydrometerโ€™s calibration/reference temperature (Tref), using consistent units (e.g., ยฐC).
  3. If your measurement is in ยฐPlato, use a suitable separate conversion before entering SG; no automatic Plato conversion is provided here.
  4. Compute the density of pure water at Tmeas and Tref, then apply: SGcorr = SGmeas ร— ฯw(Tref)/ฯw(Tmeas).
  5. If desired, convert SGcorr back to ยฐPlato.
  6. Choose Brewing hydrometer temperature in the Solve for selector, then Calculate.

Example Problem:

Use the following variables as an example problem to test your knowledge.

measured specific gravity = 1.05 SG

sample temperature (Tmeas) = 25 ยฐC

calibration temperature (Tref) = 20 ยฐC