Enter the initial amps, distance, and amp loss into the calculator to calculate the missing value.

Amp Loss Over Distance Calculator

Enter the circuit details you have, then calculate voltage drop, maximum distance, or wire size.

Voltage drop
Max distance
Wire size

Related Calculators

Amp Loss Over Distance Formula

The calculator does not reduce amps along the wire. In a closed circuit the current is the same at every point. What changes over distance is voltage. The wire has resistance, so some of the source voltage is dropped across the conductors before it reaches the load. That is what people usually mean by "amp loss over distance."

The base voltage drop formula is:

Vdrop = K * I * R * L / 1000
  • Vdrop = voltage dropped across the wire, in volts
  • K = circuit factor: 2 for DC or single-phase 2-wire, 1.732 for three-phase
  • I = load current in amps
  • R = conductor resistance in ohms per 1000 feet (copper base, multiplied by 1.64 for aluminum)
  • L = one-way wire length in feet

From that, the calculator rearranges for the other two modes.

Maximum one-way distance for a chosen drop limit:

Lmax = (Vdrop_limit * 1000) / (K * I * R)

Wire size selection picks the smallest AWG whose calculated Vdrop stays at or below your limit:

Find smallest AWG where K * I * R(awg) * L / 1000 <= Vdrop_limit

The three tabs map to those three forms. The Voltage Drop tab solves for Vdrop given a wire and length. The Max Distance tab solves for L given a drop limit. The Wire Size tab scans AWG sizes from 40 up to 4/0 and returns the first one that meets the limit.

Reference Tables

Use these values to sanity check the calculator output.

AWG Copper Ω/1000 ft Aluminum Ω/1000 ft Typical use
142.5254.1415 A branch
121.5882.6020 A branch
100.9991.6430 A branch
80.6281.0340-50 A
60.3950.6555-65 A feeders
40.2490.4170-85 A feeders
20.1560.2695-115 A feeders
1/00.0980.16125-150 A service
4/00.0490.080200 A service

Voltage drop targets vary by application. These are common limits used for design work.

Application Recommended max drop
Branch circuit (NEC informational)3%
Feeder + branch combined5%
12 V DC (RV, solar, marine)3% critical, 10% non-critical
Motor branch circuits3%
Low-voltage lighting5-10%

Worked Examples and FAQ

Example 1. A 20 A load on 12 AWG copper at 120 V, single-phase, 100 ft one-way:

Vdrop = 2 × 20 × 1.588 × 100 / 1000 = 6.35 V, or about 5.3%. That is above the 3% target, so you would either step up to 10 AWG or shorten the run.

Example 2. 30 A at 240 V single-phase, 3% drop limit, 10 AWG copper. Max drop = 7.2 V.

Lmax = (7.2 × 1000) / (2 × 30 × 0.999) = 120 ft one-way.

Does current actually drop along the wire? No. Series circuit current is constant. The wire converts a small share of voltage into heat, which is why the calculator reports voltage drop and percent drop instead of an "amp loss" number.

Why use one-way length and not total wire length? The circuit factor of 2 already accounts for the return conductor in DC and single-phase circuits. Entering total loop length would double-count it.

Why is aluminum resistance higher? Aluminum has roughly 61% the conductivity of copper. The calculator multiplies the copper resistance by 1.64 to approximate aluminum at the same AWG.

Does this account for temperature? No. Values are for conductors near 20°C / 68°F. Hot conductors have higher resistance, so real-world drop on a loaded circuit at 75°C will be a few percent higher than the calculated value.