Estimate fan shaft input power, airflow, static pressure, or fan static efficiency from the other three values. Use the same operating point for all inputs; this is a low-pressure fan estimate.

Low-pressure fan estimate. Use fan static efficiency; kW is shaft input, before motor and drive losses.

Use a value greater than 0 and at most 1; 0.65 means 65%.

CFM to kW Formula

The following rounded formula estimates fan shaft input power from airflow, fan static pressure, and fan static efficiency:

kW = 0.0001175 × CFM × P ÷ n

Variables:

  • kW is fan shaft input power in kilowatts, before motor and drive losses
  • CFM is the air flow in cubic feet per minute
  • P is the static pressure in inches of water gauge (in. w.g.)
  • n is fan static efficiency as a decimal, greater than 0 and at most 1

The retained rounded constant 0.0001175 converts CFM times inches of water to kW. NIST gives 1 CFM = 0.0004719474432 m³/s and 1 conventional inch of water approximately 249.08891 Pa. Their product is approximately 0.117557 W, or 0.000117557 kW. Airflow times static pressure is static air power; dividing by fan static efficiency gives required shaft input power. Electrical input also includes motor and drive losses.

CFM to Kilowatts Conversion Table (ΔP = 2.0 in. w.g., η = 0.65)
Air Flow (CFM) Power (kW)
1000.036
1500.054
2000.072
2500.090
3000.108
4000.145
5000.181
6000.217
7500.271
9000.325
10000.362
12000.434
15000.542
20000.723
25000.904
30001.085
35001.265
40001.446
50001.808
60002.169
Rounded to 3 decimals. Formula: kW = 0.0001175 x CFM x ΔP / η. Assumes ΔP = 2.0 in. w.g. and efficiency η = 0.65.

Fan Power vs. Air Compressor Power

This low-pressure fan approximation is not a high-pressure compressor power model. Compressor input depends on absolute pressure ratio, inlet flow conditions, thermodynamic process, and efficiency. Converting PSI to inches of water alone does not make this fan model suitable for compressor sizing.

Fan vs. Compressor: Power Formula Comparison
System Type Pressure Unit Power Formula Typical Operating Pressure
Fan / Blowerin. w.g.kW = 0.0001175 x CFM x ΔP / η0.05 to 10 in. w.g.
Air CompressorPSIRequires a compression model and inlet conditions80 to 200 PSI
1 PSI is approximately 27.68 conventional inches of water. Ideal isothermal compression work depends on the logarithm of the absolute pressure ratio; no universal linear CFM-to-PSI power conversion is provided here.

Fan Affinity Law: How Airflow Changes Affect Power

For the same fan geometry and air density at corresponding operating points, with approximately unchanged efficiency, airflow scales with speed, pressure with speed squared, and shaft power with speed cubed. Under those assumptions, a 20% airflow reduction corresponds to about 48.8% less shaft power. Arbitrary airflow changes or damper adjustments do not guarantee this relationship.

Fan Affinity Law: Airflow Ratio vs. Power Ratio (Cube Relationship)
CFM Ratio Power Multiplier Power Change Example (Base: 2,000 CFM, 1.0 kW)
50%0.125x-87.5%0.125 kW
60%0.216x-78.4%0.216 kW
70%0.343x-65.7%0.343 kW
80%0.512x-48.8%0.512 kW
90%0.729x-27.1%0.729 kW
100% (base)1.000xbaseline1.000 kW
110%1.331x+33.1%1.331 kW
120%1.728x+72.8%1.728 kW
150%3.375x+237.5%3.375 kW
200%8.000x+700%8.000 kW
Power ratio ≈ (CFM ratio)^3 at corresponding operating points for the same fan, fixed geometry and density, and approximately constant efficiency. Under those assumptions: 80% speed ≈ 80% CFM ≈ 51.2% shaft power.

Fan Efficiency by Type

At fixed airflow and pressure, shaft power is inversely proportional to fan static efficiency. Use measured or manufacturer-rated static efficiency at the operating point. The following illustrative ranges are not defaults or guaranteed ratings.

Fan Type Static Efficiency Ranges at Peak Design Point
Fan Type Static Efficiency Range Peak Static Efficiency Common Applications
Propeller / Axial40 to 65%~65%Cooling towers, low-resistance exhaust
Vane Axial65 to 80%~80%Duct systems, medium-pressure supply
Centrifugal Forward-Curved55 to 70%~70%Low-pressure residential HVAC, quiet operation
Centrifugal Backward-Curved70 to 85%~85%Commercial AHUs, industrial exhaust
Centrifugal Airfoil Blade75 to 90%~90%Premium HVAC, clean-air systems, data centers
Mixed Flow60 to 78%~78%Variable flow, moderate pressure applications
Illustrative ranges only; confirm actual static efficiency from manufacturer data at the operating point. Motor and drive losses reduce overall electrical-to-air efficiency below fan shaft efficiency.

Typical Static Pressures by Application

Static pressure is determined by duct layout, filter type and loading, coil resistance, and damper positions. The values below are illustrative references, not equipment ratings or design targets; verify the actual system pressure losses at the required airflow.

Reference Static Pressures for Common Fan Applications
Application Typical ΔP (in. w.g.) Dominant Pressure Loss Source
Residential HVAC (AHU)0.5 to 1.0Filter + coil + ductwork
Commercial AHU1.0 to 3.0Longer duct runs, VAV boxes, MERV 13+ filters
Kitchen exhaust hood0.5 to 1.5Grease filters, duct length
Industrial process exhaust1.0 to 4.0Dust collectors, long duct runs
Cleanroom supply (ISO 5-6)2.0 to 5.0HEPA filtration dominates
Cooling tower fan0.05 to 0.3Fill resistance only, very low
Data center CRAC/CRAH0.3 to 0.8Raised floor, perforated tiles
Filter loading changes the system resistance and operating point. Its effect on airflow and motor load depends on the fan curve and controls; measure or obtain system-specific data.