Calculate the power required to move air through a fan or duct system. Enter the air flow rate, static pressure in inches of water gauge, and fan efficiency to find the drive power in kilowatts.

CFM ⇆ kW Calculator

Enter any 3 values to solve for the fourth.

CFM to kW Formula

The following formula is used to convert CFM to kW:

kW = 0.0001175 * (CFM * P) / n

Variables:

  • kW is the power in kilowatts
  • CFM is the air flow in cubic feet per minute
  • P is the static pressure in inches of water gauge (in. w.g.)
  • n is the fan efficiency as a decimal (0 to 1)

The constant 0.0001175 is a unit conversion factor derived from physics: 1 CFM equals 0.000471947 m/s and 1 in. w.g. equals 249.089 Pa. Their product is 0.1175 W of theoretical air power, or 0.0001175 kW. Dividing by efficiency n converts from shaft input power to this theoretical air power output.

CFM to Kilowatts Conversion Table (ΔP = 2.0 in. w.g., η = 0.65)
Air Flow (CFM) Power (kW)
1000.036
1500.054
2000.072
2500.090
3000.108
4000.145
5000.181
6000.217
7500.271
9000.325
10000.362
12000.434
15000.542
20000.723
25000.904
30001.085
35001.265
40001.446
50001.808
60002.169
Rounded to 3 decimals. Formula: kW = 0.0001175 x CFM x ΔP / η. Assumes ΔP = 2.0 in. w.g. and efficiency η = 0.65.

Fan Power vs. Air Compressor Power

This formula applies to fans and blowers where static pressure is measured in inches of water gauge. Air compressors operate at far higher pressures measured in PSI. Since 1 PSI equals 27.68 in. w.g., applying the fan formula to a compressor system would understate actual power by roughly 28x.

Fan vs. Compressor: Power Formula Comparison
System Type Pressure Unit Power Formula Typical Operating Pressure
Fan / Blowerin. w.g.kW = 0.0001175 x CFM x ΔP / η0.05 to 10 in. w.g.
Air CompressorPSIkW = CFM x PSI x 0.000185 / η80 to 200 PSI
1 PSI = 27.68 in. w.g. The compressor formula constant (0.000185) includes thermodynamic compression work derived from isothermal compression theory.

Fan Affinity Law: How Airflow Changes Affect Power

Fan power scales with the cube of airflow (Fan Affinity Law 3). Cutting airflow by 20% reduces power by 49%. Doubling airflow requires 8 times the power. Variable frequency drives (VFDs) are specified and payback-analyzed using this cube relationship.

Fan Affinity Law: Airflow Ratio vs. Power Ratio (Cube Relationship)
CFM Ratio Power Multiplier Power Change Example (Base: 2,000 CFM, 1.0 kW)
50%0.125x-87.5%0.125 kW
60%0.216x-78.4%0.216 kW
70%0.343x-65.7%0.343 kW
80%0.512x-48.8%0.512 kW
90%0.729x-27.1%0.729 kW
100% (base)1.000xbaseline1.000 kW
110%1.331x+33.1%1.331 kW
120%1.728x+72.8%1.728 kW
150%3.375x+237.5%3.375 kW
200%8.000x+700%8.000 kW
Power ratio = (CFM ratio)^3. Valid when fan speed changes at constant system resistance. Applies directly to VFD speed reductions: 80% speed = 80% CFM = 51.2% power.

Fan Efficiency by Type

The efficiency term in the formula has a larger effect on calculated kW than any other variable at fixed CFM and pressure. Fan type selection determines the achievable efficiency range at design conditions. Off-design operation reduces efficiency below peak values.

Fan Type Static Efficiency Ranges at Peak Design Point
Fan Type Static Efficiency Range Peak Static Efficiency Common Applications
Propeller / Axial40 to 65%~65%Cooling towers, low-resistance exhaust
Vane Axial65 to 80%~80%Duct systems, medium-pressure supply
Centrifugal Forward-Curved55 to 70%~70%Low-pressure residential HVAC, quiet operation
Centrifugal Backward-Curved70 to 85%~85%Commercial AHUs, industrial exhaust
Centrifugal Airfoil Blade75 to 90%~90%Premium HVAC, clean-air systems, data centers
Mixed Flow60 to 78%~78%Variable flow, moderate pressure applications
Source: AMCA Publication 201; ASHRAE Handbook HVAC Systems and Equipment. Values are at design-point peak. Belt-drive losses (4 to 15%) and motor losses reduce system efficiency below fan shaft efficiency.

Typical Static Pressures by Application

Static pressure is determined by duct layout, filter type and loading, coil resistance, and damper positions. The values below are clean-filter design targets at rated airflow.

Reference Static Pressures for Common Fan Applications
Application Typical ΔP (in. w.g.) Dominant Pressure Loss Source
Residential HVAC (AHU)0.5 to 1.0Filter + coil + ductwork
Commercial AHU1.0 to 3.0Longer duct runs, VAV boxes, MERV 13+ filters
Kitchen exhaust hood0.5 to 1.5Grease filters, duct length
Industrial process exhaust1.0 to 4.0Dust collectors, long duct runs
Cleanroom supply (ISO 5-6)2.0 to 5.0HEPA filtration dominates
Cooling tower fan0.05 to 0.3Fill resistance only, very low
Data center CRAC/CRAH0.3 to 0.8Raised floor, perforated tiles
Dirty filter conditions increase static pressure by 0.5 to 1.5 in. w.g. above clean values, reducing airflow and increasing motor load on fixed-speed fans.