Calculate duct static pressure from CFM, duct size and total pressure, or find CFM from static pressure, for round or rectangular ducts in in. w.g. or Pa.
- All Unit Converters
- All Pressure Calculators
- FPM to CFM Calculator
- Air Flow Calculator
- Duct Velocity Calculator
- Flow Rate Pressure Calculator
- Pressure to Velocity Calculator
Calculator Functions
| Function | What it does | What it requires |
|---|---|---|
| Duct static pressure from airflow | Finds the static pressure at a point in a duct from the airflow and the total pressure there | Requires the airflow, the duct total pressure, the duct shape and inside size, and the air density |
| Airflow from duct static pressure | Finds the airflow from the gap between total and static pressure at one point in a duct | Requires the duct static pressure, the duct total pressure, the duct shape and inside size, and the air density |
Airflow goes in as CFM, m³/h or L/s, and pressures as in. w.g., Pa or mm w.g. The duct is round, sized by inside diameter, or rectangular, sized by inside width and height, in inches or millimeters. Air density starts at 1.2014 kg/m³. Every result shows static, total and velocity pressure in Pa along with the airflow in CFM.
CFM to Static Pressure Formulas
| SP | Duct static pressure (Pa) |
| TP | Duct total pressure at the same point (Pa) |
| ρ | Air density (kg/m³) |
| V | Average air velocity in the duct (m/s) |
Total pressure is the sum of static pressure and velocity pressure [2], and velocity pressure is ½ × ρ × V² [1]. Airflow in CFM does not set static pressure on its own. It sets the velocity pressure for a given duct size, and the static pressure is whatever remains of the total pressure. Pressures entered in in. w.g. are converted at 249.08891 Pa per inch, which is also 0.0361 psi [3].
Duct static pressure from airflow
Q is the airflow and A is the inside area of the duct: π ÷ 4 × diameter² for a round duct, or width × height for a rectangular one. With Q in CFM and A in ft², V is in ft/min, and multiplying by 0.00508 gives m/s. For 1,000 CFM in a 12 in by 12 in duct, V is 1,000 ft/min, or 5.08 m/s. The velocity pressure is ½ × 1.2014 × 5.08² = 15.50 Pa, or 0.0622 in. w.g. With a total pressure of 1.20 in. w.g., the static pressure is 1.20 − 0.0622 = 1.1378 in. w.g.
Airflow from duct static pressure
This is the main formula solved for velocity, and the airflow is then Q = V × A. A duct point with 1.20 in. w.g. total and 1.00 in. w.g. static has a velocity pressure of 0.20 in. w.g., or 49.82 Pa. That gives V = √(2 × 49.82 ÷ 1.2014) = 9.107 m/s, or 1,792.7 ft/min, which is 1,792.7 CFM through 1 ft² of duct. A static pressure above the total pressure is rejected.
Limits of This Estimate
- The result is the static pressure at one point in a duct. It is not a fan’s static pressure rise, the external static pressure of an air handler or the friction loss of a duct run.
- Both pressures must be measured at the same point against the same reference. Duct static pressure is negative on the suction side of a fan, and a negative value is accepted.
- The default density of 1.2014 kg/m³ is dry standard air, 0.075 lb/ft³ at 68 °F and 29.92 in. Hg [2]. Hot, cold or high-altitude air needs its own density.
- The velocity is an average across the duct, and the relation treats air as incompressible [1], which holds at ordinary duct speeds.
Sources
- NASA Glenn Research Center, Dynamic Pressure: velocity pressure as ρV² ÷ 2, and static plus velocity pressure equal to total pressure for incompressible flow
- OSHA Technical Manual, Section III, Chapter 3, Ventilation Investigation: static, velocity and total pressure in ducts, and the density of standard air
- NIST, Guide for the Use of the International System of Units (SP 811), Appendix B.8: inch and millimeter of water, psi, foot and cubic foot per minute in SI units
