Calculate a CT ratio from primary and secondary current, or find primary or secondary current from a standard ratio such as 100:5 or a custom multiplier.

For a CT’s rated ratio, enter its rated secondary: usually 5 A, or 1 A.

Optional settings

CT Ratio Formula

The CT ratio compares the primary current flowing through a current transformer to the secondary current produced by the transformer. The calculator uses amperes as the base unit, then converts a calculated current to the selected result unit.

CT Ratio = Iₚ / Iₛ
Iₚ = Iₛ × CT Ratio
Iₛ = Iₚ / CT Ratio
  • CT Ratio is the current transformer ratio, written as a number such as 100, 200, or 600.
  • I_p is the primary current.
  • I_s is the secondary current.

The calculator has three basic functions:

  • Find CT ratio: enter the primary current and secondary current. The calculator divides primary current by secondary current.
  • Find primary current: enter the secondary current and CT ratio. The calculator multiplies secondary current by the CT ratio.
  • Find secondary current: enter the primary current and CT ratio. The calculator divides primary current by the CT ratio.

If you enter values in mA or kA, the calculator first converts them to amperes:

  • mA to A: multiply by 0.001
  • kA to A: multiply by 1000

Common CT Ratio Values

Many current transformers use a 5 A or 1 A secondary current. The table below shows common CT ratios and what they mean for primary and secondary current.

CT Marking Primary Current Secondary Current CT Ratio
100/5 100 A 5 A 20
200/5 200 A 5 A 40
400/5 400 A 5 A 80
600/5 600 A 5 A 120
1000/5 1000 A 5 A 200

Current Unit Conversions

Use the same current unit on both sides when calculating by hand, or convert both values to amperes first.

Unit Meaning Conversion to A
mA milliampere 1 mA = 0.001 A
A ampere 1 A = 1 A
kA kiloampere 1 kA = 1000 A

Example CT Ratio Calculations

Example 1: Find the CT ratio

A current transformer has a primary current of 400 A and a secondary current of 5 A.

CT Ratio = 400 / 5 = 80

The CT ratio multiplier is 80, equivalently 80:1. The matching current pair is 400 A:5 A; a nameplate rating is distinct from an arbitrary measured current pair.

Example 2: Find the secondary current

A CT has a primary current of 600 A and a CT ratio of 120.

Iâ‚› = 600 / 120 = 5 A

The secondary current is 5 A.

FAQ

What does a CT ratio of 100 mean?

A CT ratio of 100 means the primary current is 100 times the secondary current. For example, if the secondary current is 5 A, the primary current is 500 A.

Is CT ratio the same as the marking on the transformer?

The marking often shows the primary and secondary current, such as 400/5. The numerical CT ratio is found by dividing those values. For 400/5, the CT ratio is 400 divided by 5, which equals 80.

Why does the secondary current matter?

The secondary current is the scaled output from the current transformer. Meters, relays, and protection devices use this smaller current instead of measuring the large primary current directly. Common secondary ratings are 5 A and 1 A.

Can you select a CT ratio from transformer kVA and voltage?

The transformer rating and voltage give you the full-load current on the side where the CT will measure current. Divide the rating in volt-amperes (kVA × 1,000) by the RMS voltage for single-phase, or by √3 times the RMS line-to-line voltage for balanced three-phase. To choose a CT, also check the maximum expected operating current, the meter or relay’s required secondary current, and the CT’s accuracy at the total connected burden. Protection applications also need a fault-current and saturation check.