Convert RMS line-to-line and phase/winding voltage for balanced, steady-state sinusoidal three-phase wye or delta systems in either direction. Optional line current gives phase current and total apparent power; a supplied power factor also gives real power.
- All Unit Converters
- All Electrical Calculators
- Line to Line Voltage Calculator
- Phase Angle Calculator
- Applied Voltage Calculator
- Phase to Ground Voltage Calculator
- Current Per Phase Calculator
Line-to-Phase Voltage Formula
For a balanced three-phase wye connection, phase/winding voltage is the line-to-neutral voltage. A delta winding is connected directly between two lines. Use the relationship for the actual connection, with RMS magnitudes:
Variables:
- Vphase is the RMS voltage across one winding or phase load (volts); it is line-to-neutral in wye, and line-to-line in delta
- VL-L is the RMS voltage between two line conductors (volts)
In balanced wye, divide line-to-line voltage by the full value of √3; reverse the conversion by multiplying phase voltage by √3. In delta, phase/winding voltage equals line-to-line voltage in either direction. These relationships do not determine general line-to-ground voltage. University of Louisville explains the balanced RMS wye and delta relationships.
| Line Voltage VLL (V) | Wye Phase / Line-to-Neutral Voltage VLN (V) |
|---|---|
| 208 | 120.089 |
| 220 | 127.017 |
| 230 | 132.791 |
| 240 | 138.564 |
| 380 | 219.393 |
| 400 | 230.940 |
| 415 | 239.600 |
| 440 | 254.034 |
| 460 | 265.581 |
| 480 | 277.128 |
| 575 | 331.976 |
| 600 | 346.410 |
| 690 | 398.372 |
| 1000 | 577.350 |
| 2400 | 1385.641 |
| 3300 | 1905.256 |
| 4160 | 2401.777 |
| 6900 | 3983.717 |
| 11000 | 6350.853 |
| 13800 | 7967.434 |
| Balanced wye only: VLN = VLL ÷ √3. Values use the full square root and are rounded to 0.001 V. Example: 480 VLL ≈ 277.128 VLN. In delta, winding voltage equals VLL. | |
How to Calculate Line-to-Phase Voltage?
The following two examples use balanced three-phase wye RMS voltages. Delta winding voltage would instead equal the entered line-to-line voltage.
Example Problem #1:
- First, use a line-to-line RMS voltage of 47 V for the balanced wye example.
- Finally, calculate the Line-to-Phase Voltage using the formula above:
Wye: Vphase = VL-L / √3
Using the full value of √3 and rounding the answer gives:
Vphase = 47 / √3 ≈ 27.135 V RMS
Example Problem #2:
Using the same process as example problem 1, we first define the variables outlined by the formula. In this case, the values are:
Line-to-line RMS voltage in the balanced wye system = 69 V.
Entering these values into the formula or calculator above gives us
Vphase = 69 / √3 ≈ 39.837 V RMS.
