Convert W/m²K U-values and thermal resistance between metric and imperial units, or solve U = 1/R and R = 1/U for whole building assemblies.

W/(m²·K) is already the SI unit of U-value. Convert it to or from imperial U-factor units here.

W/(m²·K) already measures U-value. Use a whole-assembly value, not conductivity in W/(m·K).

A change of units preserves the same thermal transmittance.

Optional settings

W/(m²·K) To U Value Formula

The following reciprocal relation calculates U-value from total assembly thermal resistance. W/(m²·K) is already a U-value unit; converting U-value units does not take its reciprocal.

U = 1 / R

Variables:

  • U is the U-value (W/m²K)
  • R is the total assembly thermal resistance (m²·K/W), including applicable surface films for the same assembly boundaries.

For matching whole-assembly boundaries, calculate U = 1 ÷ total R using consistent units. Lower U means less heat transfer per area and temperature difference. A single insulation layer does not necessarily represent a wall or window assembly: applicable surface films, framing and other heat paths also matter.

Thermal Resistance to U-Value Conversion Table (U = 1 ÷ R)
Thermal Resistance (m²K/W) U-Value (W/m²K)
0.1010.000
0.205.000
0.254.000
0.303.333
0.502.000
0.701.429
1.001.000
1.500.667
2.000.500
2.500.400
3.000.333
3.500.286
4.000.250
5.000.200
6.000.167
7.000.143
8.000.125
9.000.111
10.000.100
12.000.083
* Rounded to 3 decimals. Relation: U (W/m²K) = 1 ÷ R (m²K/W).

What Does “W/(m²·K) to U Value” Mean?

W/(m²·K), watts per square meter per kelvin, is already the SI unit of U-value (thermal transmittance). It describes heat-transfer rate per area per temperature difference. A value of 0.25 W/(m²·K) is therefore a U-value of 0.25 in SI units. To convert units, 1 Btu_IT/(h·ft²·°F) = 5.678263341113488 W/(m²·K); equivalently, multiply an SI U-value by 0.17611018368230584 for imperial units. The calculator uses International Table Btu. Fahrenheit denotes a temperature difference here, so no +32 offset applies. Conductivity in W/(m·K) is a different quantity and requires thickness and a complete assembly model before deriving U-value.

How to Calculate W/(m²·K) To U Value?

The following steps outline how to calculate the U-value (W/m²K) using the formula U = 1 / R.


  1. First, determine total thermal resistance (R) in m²·K/W for the same assembly boundaries, including applicable surface films.
  2. Next, use the formula U = 1 / R to calculate the U-value in W/m²K.
  3. Finally, check your answer with the calculator above.

Example Problem:

Use the following variables as an example problem to test your knowledge.

Thermal resistance (R) = 0.05 m²·K/W, so U = 1 ÷ 0.05 = 20 W/(m²·K).