Calculate the heat load of a room in BTU/hr, kW and tons from its size, insulation level and design temperatures, for heating or sensible cooling.

Steady heat loss; excludes solar, ducts and internal heat gains. This is not equipment sizing.

Typical design value: 70 ยฐF for heating, 75 ยฐF for cooling. Change it if yours differs.

Your local cold-day (heating) or hot-day (cooling) design temperature, e.g. the 99% winter or 1% summer value.

Illustrative U-values and air-change rates for typical construction, not tested data. Override them under the optional settings.

Envelope geometry and overrides

Blank means zero; subtracted from gross exterior wall area.

Blank means zero; subtracted from gross exterior wall area.

Blank uses the preset: 0.25 / 0.35 / 0.50 / 0.75 ACH for High performance / Good / Average / Poor. This is not ACH50.

Blank uses the illustrative preset; enter the whole-assembly U-value.

Blank uses the illustrative preset; enter the whole-assembly U-value.

Blank uses the illustrative preset; enter the whole-assembly U-value.

Blank uses the illustrative preset; enter the whole-assembly U-value.

Blank uses the illustrative preset; enter the whole-assembly U-value.

Heat Load Formula

This room model sums envelope conduction and sensible natural infiltration. Cooling mode also adds entered occupant and equipment gains. It excludes solar, latent and duct loads.

Q = ฮฃ Uแตข Aแตข ฮ” T + 1.08 dot Vโ‚แตขแตฃ ฮ” T + Qแตขโ‚™โ‚œโ‚‘แตฃโ‚™โ‚โ‚—
  • Q is the estimated room heating loss or sensible cooling load (Btu/h)
  • U is whole-assembly thermal transmittance (Btu/(hยทftยฒยทยฐF)); A is the applicable exposed area (ftยฒ)
  • Vฬ‡air is natural infiltration airflow (ftยณ/min), estimated as natural ACH ร— room volume/60
  • ฮ”T is the design temperature difference (ยฐF); internal gains are added only in cooling mode

Choose the room-load mode, enter dimensions and design temperatures, then choose an insulation level or supply project-specific overrides. The 1.08 infiltration coefficient assumes standard air conditions. This is not a Manual J or equipment-selection calculation.

Heat Load Definition

A room heat load is a rate of heat addition or removal needed to maintain its design temperature under specified conditions; it is power, not a total energy quantity.


Heat Load Example

How to calculate heat load?

  1. First, enter room dimensions.

    Use length 20 ft, width 15 ft and height 8 ft.

  2. Next, choose envelope assumptions.

    For this illustrative example use Average, two adjacent exterior walls, exposed ceiling and unexposed floor; window and door areas are zero.

  3. Next, enter design temperatures.

    Indoor 70 ยฐF and outdoor 30 ยฐF give a 40 ยฐF difference.

  4. Finally, calculate the heat load.

    Wall loss is 840 Btu/h, ceiling loss 600 Btu/h and infiltration 864 Btu/h using 0.50 natural ACH. The estimated total is 2,304 Btu/h, approximately 0.6752 kW.

FAQ

What is a heat load?

A heat load is the rate of heating or cooling required under specified conditions. This calculator estimates only the included envelope, sensible infiltration and entered cooling gains; it does not determine complete HVAC equipment capacity.


Heat Load Calculator screenshot

The following retained formula image illustrates the separate fluid-stream relation Qฬ‡ = แน Cp ฮ”T; it is not the room-load formula used above. For that calculation, use the Heat Exchanger Duty Calculator.

heat load formula