Calculate steady operating current, power or voltage for DC, single-phase AC and balanced three-phase AC. Select electrical input or motor shaft-output power; enter true power factor and motor efficiency where applicable. Breaker and conductor sizing require a separate installation-specific design.

Steady operating values only. Three-phase means balanced loads and total three-phase power. This tool does not size breakers or conductors or predict motor starting current.

AC values are RMS. For three-phase, select the voltage convention below.

Optional settings

A comparison only. Applicable wiring and protection rules depend on the installation.

Current From kW Formula

For steady DC, or single-phase AC at unity PF, use electrical real-input power in the following formula. The examples and table below use these assumptions.

Ikw = KW × 1000 / V
  • Where Ikw is the Current From kW (amps)
  • KW is electrical real-input power (kW), not motor shaft output 
  • V is the total voltage (volts) 

For DC, I = 1,000 × input kW / V. For single-phase AC, divide additionally by true PF. For balanced three-phase AC, use total input power and divide by √3 × line-to-line RMS voltage × true PF, or 3 × line-to-neutral RMS voltage × true PF. If the specified power is motor shaft output, first divide by motor efficiency to obtain electrical input. These equations calculate operating current, not starting current or breaker/wire ratings.

kW to Amps Conversion Table (Single-phase/DC, PF = 1.00)
Power (kW) Amps @ 120 V Amps @ 208 V Amps @ 230 V Amps @ 240 V Amps @ 277 V Amps @ 480 V
0.252.081.201.091.040.900.52
0.504.172.402.172.081.801.04
0.756.253.613.263.132.711.56
18.334.814.354.173.612.08
1.512.507.216.526.255.423.13
216.679.628.708.337.224.17
325.0014.4213.0412.5010.836.25
433.3319.2317.3916.6714.448.33
541.6724.0421.7420.8318.0510.42
7.562.5036.0632.6131.2527.0815.63
1083.3348.0843.4841.6736.1020.83
12.5104.1760.1054.3552.0845.1326.04
15125.0072.1265.2262.5054.1531.25
20166.6796.1586.9683.3372.2041.67
25208.33120.19108.70104.1790.2552.08
30250.00144.23130.43125.00108.3062.50
40333.33192.31173.91166.67144.4183.33
50416.67240.38217.39208.33180.51104.17
75625.00360.58326.09312.50270.76156.25
100833.33480.77434.78416.67361.01208.33
Formula: I (A) = P (kW) × 1000 / V (V). Assumes single‑phase/DC and power factor PF = 1.00.

How to Calculate Current From kW?

The following two example problems outline how to calculate the Current From kW.

Example Problem #1:

  1. First, determine the total kilowatts (kW). In this example, the total kilowatts (kW) is measured to be 5.
  2. Next, determine the total voltage (volts). For this problem, the total voltage (volts) is calculated to be 100.
  3. Finally, calculate the Current From kW using the formula above: 

Ikw = KW *1000 / V

Inserting the values from above and solving the equation with the imputed values gives: 

Ikw = 5 *1000 / 100 = 50 (amps)


Example Problem #2: 

Using the same process as example problem 1, we first define the variables outlined by the formula. In this case, the values are:

total kilowatts (kW) = 3

total voltage (volts) = 50

Entering these values into the formula above gives us 

Ikw = 3*1000 / 50 = 60 (amps)