Calculate fire load density from room type, combustible material mass, or custom energy and floor area, in MJ/m² and total MJ for any room.

Fire Load Calculator

Pick the mode that matches what you know, then hit Calculate.

By Room Type
By Material
Custom
Fire load density
▸ How this is calculated
Copy result

Fire Load Formula

Fire load density is the total combustible energy in a space divided by its floor area.

q = (Σ mᵢ × Hᵢ) / A
  • q = fire load density (MJ/m²)
  • mᵢ = mass of each combustible item (kg)
  • Hᵢ = calorific value of that material (MJ/kg)
  • A = floor area of the compartment (m²)

The "By Room Type" mode skips the summation and uses a published density value for the occupancy. The "Custom" mode lets you enter the total energy directly if you have already summed it. Results assume all listed combustibles burn completely. Structural elements such as timber framing or wall linings should be included if they can contribute to the fire.

Reference Values

Typical fire load densities by occupancy (Eurocode EN 1991-1-2 and NFPA data, 80% fractile):

Occupancy MJ/m²
Classroom215
Hotel room285
Hospital room310
Dwelling300
Office420
Warehouse (light)500
Retail / shopping600
Warehouse (heavy)1180
Library1500

Calorific values for common materials:

Material MJ/kg
Cotton / textiles16
Paper / cardboard17
Wood / timber17.5
Rubber24
PVC25
Plastics (mixed)40
Diesel / heating oil43
Petrol / polyethylene46

Worked Example

A 30 m² office contains 200 kg of timber furniture, 80 kg of paper, and 40 kg of mixed plastics.

  • Timber: 200 × 17.5 = 3,500 MJ
  • Paper: 80 × 17 = 1,360 MJ
  • Plastics: 40 × 40 = 1,600 MJ
  • Total: 6,460 MJ
  • Fire load density: 6,460 ÷ 30 = 215 MJ/m²

That sits well below the 420 MJ/m² Eurocode reference for offices, suggesting the room is lightly loaded compared to typical office stock.

FAQ

Fire load vs. fire load density? Fire load is the total energy in MJ. Fire load density divides by floor area, giving MJ/m². Density is what fire codes use because it scales with compartment size.

Should I include the building structure? Include any combustible structure that can burn during the fire, such as timber floors, joists, or wall linings. Concrete, steel, and masonry are ignored.

Why use the 80% fractile? Eurocode tables give the value that 80% of comparable rooms fall below. It is a design value, not an average, and gives a margin for rooms that are more loaded than typical.

What is the equivalent in wood? Divide MJ/m² by 17.5 to get the kg of wood per m² that would release the same energy. 420 MJ/m² ≈ 24 kg of wood per m².