Calculate maximum occupancy (fire-code occupant load) from floor area and the room’s use with IBC 2021 load factors, or enter your local code’s factor.

Area per person from IBC 2021 Table 1004.5. Net excludes walls, corridors and fixed fixtures; your local code may differ.

Optional settings


Related Calculators

Calculator Functions

FunctionWhat it doesWhat it requires
Calculate occupant loadFinds the number of people a room or building is counted as holding under a building or fire code area factorRequires the floor area and the space use
Plan floor areaFinds the floor area that a target number of people needs under the same factorRequires the target number of occupants and the space use

Space use selects one of 12 occupant load factors from the 2021 International Building Code, or a custom factor with a choice of gross or net area. Floor area can be in ftยฒ or mยฒ, and a custom factor in ftยฒ or mยฒ per person.

Fire Occupancy Formulas

OL = A รท OLF, rounded up [1]
OLOccupant load (people)
AFloor area of the space, gross or net to match the factor (ftยฒ)
OLFOccupant load factor, the floor area allowed per person (ftยฒ per person)

For areas without fixed seating, the International Building Code sets the occupant load at no less than the floor area divided by the factor for the function of the space [1]. The calculator uses these factors from its Table 1004.5:

Space useftยฒ per person
Assembly, standing space5 net
Assembly, chairs only (not fixed)7 net
Assembly, tables and chairs15 net
Classrooms20 net
Day care35 net
Exercise rooms50 gross
Mercantile (retail)60 gross
Industrial areas100 gross
Business areas (offices)150 gross
Kitchens, commercial200 gross
Residential200 gross
Warehouses500 gross
Occupant load factors from 2021 IBC Table 1004.5. The full table lists more uses.

A gross factor applies to the whole floor area of the space. A net factor applies to the occupied area only, leaving out areas such as corridors, restrooms and mechanical rooms.

Calculate occupant load

A 2,000 ftยฒ room set with tables and chairs is 2,000 รท 15 = 133.33, which the calculator rounds up to 134 people. An 1,800 ftยฒ shop is 1,800 รท 60 = 30 people. A 405 ftยฒ room with rows of loose chairs is 405 รท 7 = 57.86, so 58 people. An area in mยฒ is converted first, using 1 ftยฒ = 0.09290304 mยฒ: a 100 mยฒ classroom is 1,076.39 ftยฒ รท 20 = 53.82, so 54 people.

Plan floor area

A = people ร— OLF

An office for 100 people at 150 ftยฒ per person is 100 ร— 150 = 15,000 ftยฒ of gross floor area. Standing space for 50 people is 50 ร— 5 = 250 ftยฒ net. This reverses the area arithmetic only: exits and other requirements can limit a space to fewer people than its area allows.

How to Calculate Occupancy by Fire Code

Measure the floor area of the room, find the occupant load factor for how the room is used in the code your jurisdiction has adopted, and divide the area by the factor. Rooms with fixed seats are counted by the number of seats instead, with one person per 18 in of bench or pew [1]. Where a space has more than one use, each area is calculated with its own factor and the results are added [1]. The code allows a higher posted number if every other requirement is met for it, up to one person per 7 ftยฒ [1]. Assembly rooms must have their occupant load posted near the main exit [1]. The local building official or fire marshal sets the approved figure.

Limits of This Estimate

  • This is an area-factor calculation only, and the result is not an approved occupancy limit. Exits, fixed seating, other code provisions and the authority having jurisdiction determine the permitted occupancy.
  • The preset factors are from the 2021 International Building Code. States, cities and other countries adopt different editions and amendments, and some use other codes such as NFPA 101, so the local factor can differ.
  • The area must match the factor: gross area for a gross factor and net area for a net factor. Using gross area with a net factor overstates the occupant load.

Sources

  1. International Code Council, 2021 International Building Code, Chapter 10, Section 1004 and Table 1004.5: occupant load from floor area and factor, the factors, fixed seating, multiple functions, increased occupant load and posting