Enter the net reactance (Ω) and RMS current (A) of a single‑phase circuit (or per phase of a balanced three‑phase circuit) into the calculator to determine the kilovolt-ampere reactive (kVAR).

KVAR Calculator

X-I-kVAR
Power Factor Correction
Capacitor Sizing
kW‑kVA‑kVAR

Enter any 2 values to calculate the missing variable (assumes RMS values; X in Ω and result in kVAR).

KVAR Formula

The following formulas are used to calculate reactive power. When reactance X is in ohms (Ω) and current I is in amps (A), the result of X·I² is in VAR (volt‑ampere reactive). Divide by 1000 to convert to kVAR.

Q(\mathrm{VAR}) = X I^2
\mathrm{kVAR} = \frac{X I^2}{1000}
  • Where Q is the reactive power in VAR
  • kVAR is reactive power expressed in kilovolt‑ampere reactive (1 kVAR = 1000 VAR)
  • X is the (net) reactance of the system (ohms)
  • I is the RMS current of the system/circuit (amps)

To calculate the reactive power in kVAR, multiply the reactance by the current squared, then divide by 1000.

KVAR Definition

What is KVAR?

kVAR (kilovolt‑ampere reactive) is a unit used to express electrical reactive power in AC power systems. Reactive power is associated with energy that oscillates between the source and reactive components (inductors and capacitors), and it is commonly discussed in power factor correction and capacitor bank sizing. (1 kVAR = 1000 VAR.)

Example Problem

How to calculate KVAR?

  1. First, determine the reactance of the savings system.

    For this problem, the reactance is calculated to be 40 ohms.

  2. Next, determine the current of the system.

    For this example, the current of the circuit is measured to be 150 amps.

  3. Finally, calculate the KVAR.

    Using the formula above, the kVAR is calculated to be:
    kVAR = (X · I^2) / 1000
    kVAR = (40 · 150^2) / 1000
    kVAR = 900 kVAR