Find how much weight a roof can hold per square foot from its rafter size, spacing, span and lumber grade, or the longest span for a snow or live load.

Snow or live load the rafters can carry per square foot of roof, on top of the roof’s own weight.

Measured level from support to support, not along the slope. 14 ft 6 in is 14.5 ft.

Printed on the lumber grade stamp.

Roof weight and area (optional)
The roof’s own weight per square foot of level area. Leave blank for 10 psf, the lightest dead load in the AWC rafter tables.

To total the weight over the roof. Use the level footprint, not the sloped surface.

Calculator Functions

The calculator checks one rafter the way the American Wood Council span tables do: for bending strength under the total roof load, and for stiffness under the snow or live load. Select a function to open it in the calculator.

FunctionUse it whenYou enter
Load the roof can holdYou know the rafters and how far they spanRafter size and spacing, the level span and the lumber grade
Maximum rafter spanYou know the snow or live load the roof must carryRafter size and spacing, the load and the lumber grade

Each lumber grade fills in its design values from the AWC tables. Choose Custom Fb and E to use values from a grade stamp or another table. The roof’s own weight, its dead load, is 10 psf unless you change it under the optional settings.

Roof Load Formulas

qb = 144 × 8FbS ÷ (sL²) − qd
qΔ = 144 × 384EI ÷ (5DsL³) [3]
qbSnow or live load bending strength allows, psf
qΔSnow or live load the deflection limit allows, psf
qdDead load, the roof’s own weight, psf
Fb, EBending design value and modulus of elasticity of the lumber, psi
S, ISection modulus b × d² ÷ 6 (in³) and moment of inertia b × d³ ÷ 12 (in⁴), with b = 1.5 in and d the actual depth
s, LRafter spacing and horizontal span, both in inches
DDeflection limit: 240 for L/240 or 180 for L/180

Both come from the formulas for a simple beam with a uniform load: the largest bending moment is wL²/8 and the largest deflection is 5wL⁴/384EI [3]. Here w is the load on each inch of rafter, the roof load in psf times the spacing ÷ 144. As in the AWC rafter tables, bending is checked under the snow or live load plus the dead load, deflection under the snow or live load alone, and the span is measured on the horizontal projection [1]. The smaller of qb and qΔ is the load the roof can hold.

Lumber design values

The calculator uses the snow-loading bending values from AWC Table W-1. They already include the adjustment for repetitive members spaced 24 in or less, and they change with the size of the lumber [2].

SizeDouglas fir-larch No. 2Douglas fir-larch No. 1Southern pine No. 2Spruce-pine-fir No. 1/No. 2
2×41,7851,9851,4551,735
2×61,5451,7201,3251,505
2×81,4301,5851,2251,390
2×101,3101,4551,0601,275
2×121,1901,3259901,155
E, all sizes1,600,0001,700,0001,400,0001,400,000
Fb for snow loading and E, in psi [2]

Deflection limits and minimum roof loads

The International Residential Code limits deflection under live load to L/180 for rafters steeper than 3:12 with no finished ceiling attached, and to L/240 under gypsum board ceilings and for most other members [4]. A roof must be designed for the code’s minimum roof live load or the ground snow load, whichever is greater. The minimum is 20 psf for a flat roof or one with less than 4 in of rise per foot, when a member carries 200 ft² of roof or less; it falls to 16 or 12 psf on steeper roofs and larger areas [4].

Worked example

Take Douglas fir-larch No. 2 2×8 rafters at 16 in on center, spanning 14 ft (168 in) measured level, with a 10 psf roof and a ceiling attached (L/240). A 2×8 has S = 13.141 in³ and I = 47.635 in⁴. Bending allows 8 × 1,430 × 13.141 × 144 ÷ (16 × 168²) = 47.9 psf in total, or 37.9 psf once the 10 psf dead load is taken off. Deflection allows 384 × 1,600,000 × 47.635 × 144 ÷ (5 × 240 × 16 × 168³) = 46.3 psf. Bending governs, so the roof can hold about 37.9 psf of snow or other live load, or 50.6 lb on each foot of rafter.

As a check against the published tables: AWC Table R-1 (20 psf live load, 10 psf dead load, L/240) lists a 14 ft 10 in span for 2×8 rafters at 16 in with Fb = 1,000 psi, which needs E = 820,000 psi [1]. The Maximum rafter span function gives 14 ft 9.6 in for the same values, within half an inch of the table.

Limits of This Estimate

  • Like the AWC tables, it checks bending and deflection of sound rafters under an even load on a single span. Notches, rot, splices, heavy point loads such as equipment, and the bearing, connections and ridge are not checked.
  • Manufactured trusses and I-joists are designed by their makers and cannot be checked with lumber design values.
  • Snow does not always settle evenly. Where it drifts against a higher wall or slides from an upper roof, part of the roof carries more than the average load.
  • Local building departments set the design snow load. Before adding weight to a roof or repairing damaged framing, have a structural engineer or the building department confirm the framing.

Sources

  1. American Wood Council, Span Tables for Joists and Rafters, 2024 Edition: how rafter spans are calculated and measured, the loads and deflection limits of the rafter tables, and Table R-1
  2. American Wood Council, Design Values for Joists and Rafters, 2024 Edition: Table W-1 bending design values for snow loading and modulus of elasticity by species, grade and size
  3. American Wood Council, Design Aid No. 6, Beam Design Formulas with Shear and Moment Diagrams: maximum moment and deflection of a simple beam with a uniformly distributed load
  4. International Code Council, 2021 International Residential Code, Chapter 3: Section R301.6 and Table R301.6 minimum roof live loads, Table R301.7 allowable deflection