Calculate 3 phase current in amps from kW, kVA or motor hp at common voltages, or find kW and kVA from amps, using a typical power factor you can change.
Related Calculators
- All Physics Calculators
- All Electrical Calculators
VA to Voltage Calculator
Phase to Ground Voltage Calculator
Total Current Calculator
Air Conditioner Current Calculator
Motor Current Calculator
Line Current Calculator
Line to Phase Current Calculator
Current Per Phase Calculator
Calculator Functions
| Function | What it does | What it requires |
|---|---|---|
| Current from power | Finds the current in each line conductor of a balanced three-phase load | Requires the power in kW, W, kVA or motor hp, the voltage and, except for kVA, the power factor |
| Power from current | Finds the real and apparent power that a line current delivers | Requires the line current, the voltage and the power factor |
The voltage is picked from 208, 230, 240, 380, 400, 415, 440, 480 or 600 V, or typed in volts or kilovolts. It can be marked as line-to-line or as line-to-neutral for a wye system. Power factor is entered as a ratio or a percent and starts at 0.85. With motor horsepower, an optional motor efficiency is used, and a blank means 90%.
3 Phase Current Formulas
(√3 × V × PF) [1]
| I | RMS current in each line (A) |
| kW | Electrical input power |
| V | Line-to-line RMS voltage (V) |
| PF | Power factor, as a decimal |
This is the three-phase power equation, kW = V × I × PF × √3 ÷ 1,000, solved for current [1]. A line-to-neutral voltage is multiplied by √3 first to give the line-to-line voltage [2], so 230 V line-to-neutral is treated as 398.4 V.
Current from power
With kW or W, the main formula applies directly. A 10 kW heater has a power factor of 1 and draws 12.03 A at 480 V, 14.43 A at 400 V and 27.76 A at 208 V.
Apparent power already includes the power factor, so none is asked for. A 63 kVA supply at 400 V is 90.93 A per line.
Motor horsepower is output power, so it is converted to input kW with the efficiency η as a decimal and then put through the main formula. A 50 hp motor at 90% efficiency takes 41.43 kW, which is 58.62 A at 480 V and a power factor of 0.85.
Power from current
Real power is then kW = kVA × PF, and reactive power is kVA × √(1 − PF²). A line current of 100 A at 480 V is 83.14 kVA. At a power factor of 0.85 that is 70.67 kW and 43.80 kvar.
Limits of This Estimate
- The formulas are for a balanced load with sine-wave voltage and current. Unequal phase loads and harmonic currents are not modelled.
- The 0.85 power factor and 90% motor efficiency are starting values. The figures on the motor nameplate give a closer result.
- The result is the running current. It does not size breakers, conductors or motor protection, which follow the electrical code.
Sources
- U.S. Department of Energy, Determining Electric Motor Load and Efficiency: three-phase power from voltage, current and power factor, and motor input power from horsepower and efficiency
- Schneider Electric, Electrical Distribution Fundamentals Design Guide, Electric Power Fundamentals: line-to-line voltage as line-to-neutral voltage times √3 in a wye system
