Calculate pipe heat loss per foot for an insulated or bare pipe from the pipe size, temperatures, and insulation type and thickness, in Btu/h or watts.

Heat loss through pipe insulation and its outer surface.

Nominal steel pipe sizes with their outside diameters. Choose Custom for copper tube or other sizes.

Temperature of the pipe wall, usually taken as the fluid temperature.

70 °F is a typical indoor value. Enter the air temperature around the pipe.

k in Btu·in/(h·ft²·°F): the most each material standard allows near room temperature. Hot service runs higher.

Length and surface (optional)
Adds the total loss for the run. Blank shows the loss per foot only.

Heat transfer from the outer surface to the air. Blank uses 1.0, a still-air estimate. Wind raises it.

Calculator Functions

The calculator estimates the steady heat loss from a pipe in Btu/h per foot and W/m, and the total for a run if you enter its length. Select a function to open it in the calculator.

FunctionUse it whenYou enter
Insulated pipeThe pipe has insulation, or you are choosing a thicknessPipe size, pipe and air temperatures, insulation type and thickness
Bare pipeThe pipe is uninsulatedPipe size, pipe and air temperatures

Pipe sizes from ½ in to 12 in fill in the outside diameter [2], and a custom diameter covers copper tube and other sizes. Temperatures can be in °F or °C. A pipe colder than the air is reported as heat gain. The insulated result also shows the insulation surface temperature and the reduction compared with the same pipe left bare.

Pipe Heat Loss Formulas

q = ΔT ÷ (Ri + Rs) [1]
Ri = ln(r₂ ÷ r₁) ÷ (2πk)
Rs = 1 ÷ (2π r₂ h)
qHeat loss per unit length of pipe (W/m, shown also in Btu/h per ft)
ΔTPipe temperature minus air temperature
RiResistance of the insulation layer
RsResistance between the outer surface and the air
r₁Pipe outside radius, which is the inside radius of the insulation
r₂Outside radius of the insulation, r₁ plus the thickness
kThermal conductivity of the insulation
hSurface coefficient for convection and radiation combined. The calculator uses 1.0 Btu/h·ft²·°F if you leave it blank [2]

Insulated pipe

The formula above applies directly. Heat flows outward through a growing area, so the insulation resistance depends on the logarithm of the radius ratio and not on thickness alone [1]. The same 1 in of insulation therefore resists less on a large pipe than on a small one. The surface temperature is the air temperature plus q × Rs.

Each insulation choice uses the highest conductivity its material standard allows, in Btu·in/(h·ft²·°F): 0.25 for fiberglass or mineral fiber, 0.28 for elastomeric foam, 0.35 for polyethylene foam, 0.20 for polyisocyanurate and 0.41 for calcium silicate [3]. Enter a custom conductivity if you have the manufacturer's value.

Bare pipe

q = h × π × D × ΔT [2]

D is the pipe outside diameter, so π × D is the surface area per unit length. The surface coefficient starts at 2.5 Btu/h·ft²·°F, which reproduces published losses for bare steel pipe at 180 to 280 °F in still air to within roughly 20% [2]. A 2 in pipe at 180 °F in 80 °F air comes out near 155 Btu/h per ft, against a published 141.

Limits of This Estimate

  • The surface coefficient is not a constant. It changes with surface temperature, air movement, pipe orientation and surface finish [2]. Wind raises it, and bare pipes above about 300 °F lose more than the 2.5 default predicts.
  • Insulation conductivity rises with temperature. The presets are rated near room temperature [3], so losses from steam and other hot lines run higher than shown unless you enter a conductivity for the operating temperature.
  • The pipe wall is taken to be at the fluid temperature along the whole run. Fittings, valves, hangers, gaps and wet insulation add losses the formula leaves out.
  • The result is a steady-state heat flow. It does not give the temperature drop of the fluid along the pipe or the time for a pipe to cool or freeze.

Sources